A workshop motor on 230 V, 50 Hz mains behaves like $8\ Ω$ of resistance in series with $19.1\ \text{mH}$ of inductance. It draws 23 A, but only 80 % of that current does useful work: the rest sloshes back and forth to build the magnetic field. Its power factor is 0.8.

The utility charges for that wasted current, and the cables must carry it. A capacitor in parallel with the motor can supply the magnetic field's reactive current locally, so the mains only supplies the real power.

How to do it:
1. Find the motor's reactance: X = 2π × 50 × 0.0191 (about 6 Ω). With R = 8 Ω, its impedance is √(8² + 6²) = 10 Ω.
2. The reactive part of the motor's admittance is X ÷ |Z|² = 6 ÷ 100 = 0.06 siemens.
3. A capacitor cancels it when 2π × 50 × C = 0.06. Solve for C.
4. Add a capacitor (right-click the canvas, then Passive Components, then Capacitor) from the top wire to the bottom wire beside the motor, so it is in parallel, and set its value.
5. Press Check answer.
Principles it rests on
Impedance, admittance and reactive power; power factor correction cancels inductive susceptance with capacitive susceptance.
Question
Add a capacitor in parallel with the motor so its power factor becomes 1 (C between 180 µF and 202 µF).

Join free to take this activity

Anyone can look around, but taking an activity needs a free account. With one, your answers are checked step by step and your progress is saved, so you can stop and pick up where you left off on any device.

It is part of the course Electrical engineering: from first circuits to the power grid.

Nobody has tried this yet.Be the first. Your answer starts the stats.

Only each person's first answer, given before viewing the solution, is counted.